Measurement line type: 

Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel (must be synchronized to reference channel during AC/DC measurement)

Voltage measurement: 600.00 V rms, Transient measurement 6.0000 kV peak

Current ranges: 500.00 mA to 5.0000 kA AC (depends on current sensor in use)

Basic accuracy:

Voltage: ±0.1% of nominal voltage
Current: ±0.2% rdg. ±0.1% f.s. + current sensor accuracy
Active power: ±0.2% rdg. ±0.1% f.s. + current sensor accuracy

Measurement items:

Transient over voltage : 2MHz sampling.

Frequency cycle : Calculated as one cycle, 40 to 70Hz

Voltage (1/2) RMS: one cycle calculation refreshed every half cycle.
Current (1/2) RMS: half-cycle calculation.

Voltage swell, Voltage dips, Voltage interruption

Inrush current

Voltage waveform comparison

Instantaneous flicker value: As per IEC61000-4-15

Frequency: Calculated as 10 or 12 cycles, 40 to 70Hz

10-sec frequency: Calculated as the whole-cycle time during the specified 10s period, 40 to 70Hz

Voltage waveform peak, Current waveform peak

Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Reactive energy, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor (negative-phase, zero-phase)

High-order harmonic component (voltage/ current): 2kHz to 80kHz

Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50th orders

Harmonic voltage-current phase angle: 1th to 50th orders

Total harmonic distortion factor (voltage/ current)

Inter harmonic (voltage/ current): 0.5Hz to 49.5Hz

K Factor (multiplication factor)

IEC Flicker, Δ V10 Flicker

Record:

55 weeks (with repeated recording set to [1 Week], 55 iterations)
35 days (with repeated recording set to [OFF])

Interface: SD/SDHC card, RS-232C, LAN (HTTP server funtion), USB2.0

Display : 6.5-inch TFT color LCD (640×480 dots)

Power supply: AC ADAPTER Z1002 (12V DC, Rated power supply 100V AC to 24 V AC, 50/60Hz)
BATTERY PACK Z1003 (Ni-MH 7.2V DC 4500mAh)

Dimensions, mass: 300mm(11.81in)W × 211mm(8.31in)H × 68mm(2.68in)D (excluding protrusions), 2.6kg(91.7oz) (including battery pack)

Supplied accessories”:

 Instruction manual×1, Measurement guide×1, VOLTAGE CORD L1000×1 set, Spiral Tube×1, Input Cable Labels×1, AC ADAPTER Z1002×1, Strap×1, USB cable (1m 3.28ft length)×1, BATTERY PACK Z1003×1, SD MEMORY CARD 2GB Z4001×1, PQA-HiView Pro 9624-50

 

Option

With 9694 sensor: 5.0000/50.000 Arms
With 9660 sensor: 50.000/100.00 Arms
With 9661 sensor: 50.000/500.00 Arms
With 9667 sensor: 50.000/500.00 A, 500.00 A/5.0000 kArms
With 9669 sensor: 100.00 A/1.0000 kArms

With 9675/9657-10 sensor: 500.00 mA/5.0000 Arms



Details
Measurement line type Single-phase 2-wire, Single-phase 3-wire, Three-phase 3-wire or Three-phase 4-wire plus one extra input channel (must be synchronized to reference channel during AC/DC measurement)
Voltage ranges Voltage measurement: 600.00 V rms
Transient measurement 6.0000 kV peak
Current ranges 500.00 mA to 5.0000 kA AC (depends on current sensor in use)
Basic accuracy Voltage: ±0.1% of nominal voltage
Current: ±0.2% rdg. ±0.1% f.s. + current sensor accuracy
Active power: ±0.2% rdg. ±0.1% f.s. + current sensor accuracy
Measurement items
  1. Transient over voltage : 2MHz sampling.
  2. Frequency cycle : Calculated as one cycle, 40 to 70Hz
  3. Voltage (1/2) RMS: one cycle calculation refreshed every half cycle.
    Current (1/2) RMS: half-cycle calculation.
  4. Voltage swell, Voltage dips, Voltage interruption
  5. Inrush current
  6. Voltage waveform comparison
  7. Instantaneous flicker value: As per IEC61000-4-15
  8. Frequency: Calculated as 10 or 12 cycles, 40 to 70Hz
  9. 10-sec frequency: Calculated as the whole-cycle time during the specified 10s period, 40 to 70Hz
  10. Voltage waveform peak, Current waveform peak
  11. Voltage, Current, Active power, Apparent power, Reactive power, Active energy, Reactive energy, Power factor, Displacement power factor, Voltage unbalance factor, Current unbalance factor (negative-phase, zero-phase)
  12. High-order harmonic component (voltage/ current): 2kHz to 80kHz
  13. Harmonic/ Harmonic phase angle (voltage/ current), Harmonic power: 0th to 50th orders
  14. Harmonic voltage-current phase angle: 1th to 50th orders
  15. Total harmonic distortion factor (voltage/ current)
  16. Inter harmonic (voltage/ current): 0.5Hz to 49.5Hz
  17. K Factor (multiplication factor)
  18. IEC Flicker, Δ V10 Flicker
Record 55 weeks (with repeated recording set to [1 Week], 55 iterations)
35 days (with repeated recording set to [OFF])
Interface SD/SDHC card, RS-232C, LAN (HTTP server funtion), USB2.0
Display 6.5-inch TFT color LCD (640×480 dots)
Power supply AC ADAPTER Z1002 (12V DC, Rated power supply 100V AC to 24 V AC, 50/60Hz)
BATTERY PACK Z1003 (Ni-MH 7.2V DC 4500mAh)
Dimensions, mass 300mm(11.81in)W × 211mm(8.31in)H × 68mm(2.68in)D (excluding protrusions), 2.6kg(91.7oz) (including battery pack)
Supplied accessories Instruction manual×1, Measurement guide×1, VOLTAGE CORD L1000×1 set, Spiral Tube×1, Input Cable Labels×1, AC ADAPTER Z1002×1, Strap×1, USB cable (1m 3.28ft length)×1, BATTERY PACK Z1003×1, SD MEMORY CARD 2GB Z4001×1