For full functionality of this site it is necessary to enable JavaScript.

KEP HVTS-HP-100/100-7.5High Voltage Tester (AC100KV/ DC100KV)

 

Details

  Datasheet

The insulators testing device HVTS-HP is designed for testing the insulation of power cables and solid dielectric with the rectified voltage of up to 100 kV, as well as testing solid dielectrics with the sinusoidal voltage of up to 100 kV, 50 Hz.

The main difference between series devices HVTS-HP devices from HVTS-70/50 is the increased power output. There are two standard versions: 7.5 KVA and 17.5 KVA.

 

  • Technical Specifications

Parameter

HVTS-HP
70/55-7,5 (17,5)

HVTS-HP
70/100-7,5 (17,5)

HVTS-HP
100/100-7,5 (17,5)

HVTS-HP
140/100-7,5 (17,5)

Output test AC voltage range, kV

0.5 – 55

1 – 100

Output test DC voltage range, kV

0.5 – 70

1 – 100

1 – 140

Output test AC current, mA, max

130 (300)

75 (175)

Output test DC current, mA, max

90 (200)

30 (65)

40 (90)

55 (125)

Output AC voltage measuring range, kV

3 – 55

3 – 100

Output DC voltage measuring range, kV

3 – 70

3 – 100

3 – 140

Output AC current measuring range, mA

1 – 130

(1 – 300)

1 – 75 (1 – 175)

Output DC current measuring range, mA

1 – 90

(1 – 200)

1 – 30

(1 – 65)

1 – 40

(1 – 90)

1 – 55

(1 – 125)

Measuring accuracy

3 % (of full scale)

Supply voltage, V

220 ± 22

Frequency, Hz

50 ± 1

  • In parentheses are the parameters for the performance of 17.5 kVA version.
  •  
  • Operating Conditions

The device is designed for an indoors operation under the following conditions:

Condition

Value

Air temperature, °С

from -10 to +40

Relative humidity, %, up to

80 at +25° С

Atmospheric pressure, kPa (mm hg)

84,0 – 106,7 (630 – 800)

 

  • Package Contents

Component

Quantity

HVTS-HP-100/100-7,5 control unit with voltage regulator VT-40 on the mobile trolley

1

TIOG-100 on the mobile trolley bundled with voltage divider, earthing and rectifier

1

Power cable on the drum (length 10 m, cross-section 4x4 mm2)

1

Grounding cable on the drum (length 10 m, cross-section 10 mm2)

2

High voltage cable on the drum (length 10 m, U test = 70 kV)

1

 

Documentation

Manual

1

  • Quality Engagement
  • Easy change and return
  • Delivery Avaliable
  • Favorable payment

Apply your mail to get promotion information