Model: MIC-5010
Manufacture: SONEL – ba lan
Insulation resistance measurement (two-lead)
Measurement range acc. to IEC 61557-2: 50k…15,0 TΩ (IISOnom = 1,2 mA or 3 mA)
Range/    Resolution
0,0...999 kΩ/    1 kΩ
1.00...9,99 MΩ/    0,01 MΩ
10.0...99,9 MΩ/    0,1 MΩ
100...999 MΩ/    1 MΩ
1.00...9,99 GΩ/    0,01 GΩ
10.0...99,9 GΩ/    0,1 GΩ
Accuracy:±(3% m.v. + 10 digits)
100...999 GΩ/    1 GΩ/    Accuracy:±(3.5% m.v. + 10 digits)
1.00...9,99 TΩ/    0,01 TΩ/Accuracy:±(7.5% m.v. + 10 digits)
10.0...15,0 TΩ/    0,1 TΩ/    Accuracy:±(10% m.v. + 10 digits)
Values of measured resistance depending on measurement voltage
Voltage UISO    /Measurement range
250 V    /500 GΩ
500 V    /1.00 TΩ
1000 V    /2.00 TΩ
2500V    /5.00 TΩ
5000V    /15.0 TΩ
Measurement of leakage current
 Range      /Resolution    /Accuracy
0…Ilmax  /m, µ, n [A]         /Calculated basing onresistance measurements
• ILmax – maximum current at short circuit of leads,
• resolution and units result from the measurement range of individual insulation resistance.
Step voltage insulation resistance measurement
Target voltage/    Measurement voltage sequence
1 kV/    200, 400, 600, 800, 1000 V
2.5 kV/    0.5, 1, 1.5, 2, 2.5 kV
5 kV/    1, 2, 3, 4, 5 kV
• duration of each "step" adjustable from 30s to 5mins
• measurement result for each voltage step is stored in memory
Continuity measurement of protective connections and equipotential bonding with 200 mA current
Measurement range acc. to EN 61557-4: 0,12...999 Ω
Range          /Resolution /    Accuracy
0.00...19.99 Ω /0,01 Ω/    ±(2% m.v. + 3 digits)
120.0...199.9 Ω/0,1 Ω /    ±(2% m.v. + 3 digits)
200...999 Ω    /1 Ω   /±(4% m.v. + 3 digits)
• Voltage on open terminals: 4...24 V
• Output current at R < 2 Ω: Imin > 200 mA (ISC: 200...250 mA)
• Compensation of test lead resistance
• Current flowing in both directions, mean value of resistance is displayed
Capacity measurement
Range/    Resolution/ Accuracy
1...999 nF     /1 nF   /±(5% m.v. + 5 digits)
1.00...49.99 µF/0.01 µF/±(5% m.v. + 5 digits)   
Capacity measurement result is displayed after the RISO measurement
DC and AC voltage measurement
Range/    Resolution/    Accuracy
0.0...29.9 V/    0.1 V/    ±(2% m.v. + 20 digits)
30.0...299.9 V/    0.1 V/    ±(2% m.v. + 6 digits)
300...600 V/    1 V/    ±(2% m.v. + 2 digits)